Skip Links

USGS - science for a changing world

Open-File Report 2011–1019

Prepared in cooperation with the U.S. Environmental Protection Agency and the New Hampshire Department of Environmental Services

Geophysical and Flow-Weighted Natural-Contaminant Characterization of Three Water-Supply Wells in New Hampshire

By Thomas J. Mack, Marcel Belaval, James R. Degnan, Stephen J. Roy, and Joseph D. Ayotte

Thumbnail of and link to report PDF (950 KB)

Abstract

Three bedrock water-supply systems in New Hampshire were studied, using borehole geophysics and flow-weighted sampling techniques, to determine the sources and distribution of natural contaminants in water entering the boreholes and to assess whether borehole modifications might be used to reduce contaminant levels. Well water in more than 100 community water-supply systems in New Hampshire have natural contaminants, such as arsenic and uranium, above the U.S. Environmental Protection Agency maximum contaminant levels of 10 and 30 micrograms per liter, respectively. The water-system wells were studied to identify fractional contributions of natural contaminants from specific fracture zones. The yields and flow-weighted contaminant levels of such fracture zones were assessed to determine if a modification of the borehole might lead to a reduction in the system’s contaminant levels.

The water-supply systems investigated were typical of small community water systems in New Hampshire where a water system may serve 100 connections or less. Each water system consisted of two wells, approximately 300 to 400 feet deep, in generally low-yielding (about 10 gallons per minute or less) crystalline bedrock. The wells were typically operated a few hours per day to fill a storage tank and had tens of feet of drawdown caused by the low well yields. The systems selected had contaminant concentrations slightly above MCL, or a low-level contamination. One of the water systems investigated had low-level (10 to 24 micrograms per liter) arsenic contamination, and two of the water systems had low-level uranium (30 to 40 micrograms per liter) contamination. The contaminant values were blended-water concentrations from the two wells in a system. Each water system had differences in contaminant concentrations between the two wells. In each case, the well with the greater concentration of the two was selected for investigation. In two of the three systems investigated, there was either not enough variation in the borehole contaminant concentration or not enough water-yielding fractures for borehole modifications to be a viable potential remedy to elevated contamination. However, borehole and contaminant conditions in one of the bedrock supply-well systems may be favorable to potential improvement of supplied water by borehole modification where selected fracture zones are sealed off from supplying water to the well.

Revised June 6, 2011

First posted February 2011

For additional information contact:
Director,
New Hampshire-Vermont Water Science Center
331 Commerce Way, Suite 2 Pembroke, NH 03275
http://nh.water.usgs.gov/

Part or all of this report is presented in Portable Document Format (PDF); the latest version of Adobe Reader or similar software is required to view it. Download the latest version of Adobe Reader, free of charge.


Suggested citation:

Mack, T.J., Belaval, Marcel, Degnan, J.R., Roy, S.J., and Ayotte, J.D., 2011, Geophysical and flow-weighted natural-contaminant characterization of three water-supply wells in New Hampshire: U.S. Geological Survey Open-File Report 2011–1019, 20 p., at https://pubs.usgs.gov/of/2011/1019/.


Contents

Acknowledgments

Abstract

Introduction

Purpose and Scope

Description of Study Area

Previous Investigations

Methods and Approach

Borehole Geophysics

Groundwater Sampling and Water-Quality Analysis

Borehole Flow and Water Quality Characterization

Francestown

Borehole Geophysical Logs

Water Quality and Flow-Weighted Chemical Constituents

Londonderry

Borehole Geophysical Log Analysis

Water Quality and Flow-Weighted Chemical Constituents

Salem

Borehole Geophysical Log Analysis

Water Quality and Flow-Weighted Chemical Constituents

Limitations and Alternatives to the Methods Used

Summary and Conclusions

References Cited

Appendix 1. Sampling Time, Depth, Contaminant Concentration, and Field Parameters for Water Sampled from Wells in Francestown, Londonderry, and Salem, New Hampshire